Operation and Installation ManualFSS Series 1.5 to 10 hpFountain Solution SystemsImportant! Read Carefully Before Attempting to Install or Operate Eq
FSS Series Fountain Solution Systems Page 9IAE-600portable models, and a 35-gallon stainless steel tank is used on the
Page 10 FSS Series Fountain Solution SystemsIAE-600Refrigeration Features• R-22 refrigerant• Hot gas bypass capacity control• High and low refriger
FSS Series Fountain Solution Systems Page 11IAE-600Process Solution Return FilterAlso Available as Field Retrofit KitT
Page 12 FSS Series Fountain Solution SystemsIAE-600Compressor Hour MeterAlso Available as Field Retrofit KitThe Compressor Hour Meter option includes
FSS Series Fountain Solution Systems Page 13IAE-600Figure 1FSS Series 1.5 hp CirculatorPortable Fountain Solution Cont
Page 14 FSS Series Fountain Solution SystemsIAE-600Figure 2FSS Series 3.5 hp CirculatorPortable Fountain Solution Control with Integral Water-Cooled C
FSS Series Fountain Solution Systems Page 15IAE-600Figure 3FSS Series 5 hp CirculatorFountain Solution System with Int
Page 16 FSS Series Fountain Solution SystemsIAE-600 Figure 4FSS-R Remote Condenser Assembly ModelsTo convert inches to cm, multiply dimension by 2.54.
FSS Series Fountain Solution Systems Page 17IAE-6002 Shipping Information2-1 Unpacking and InspectionYou should inspec
Page 18 FSS Series Fountain Solution SystemsIAE-6002-3 If the Shipment is Not CompleteCheck the packing list. You should have:; AEC, Inc./ Fountain S
Page 2 FSS Series Fountain Solution SystemsIAE-600Write down your Circulators ________________ ________________serial numbers here for _______________
FSS Series Fountain Solution Systems Page 19IAE-6002-6 UncratingFSS Series Portable Chiller Models 2 hp to 5 hpFSS Ser
Page 20 FSS Series Fountain Solution SystemsIAE-600- Notes-
FSS Series Fountain Solution Systems Page 21IAE-6003 Installation3-1 Making Electrical ConnectionsCheck serial tag vol
Page 22 FSS Series Fountain Solution SystemsIAE-6003-2 Making Process ConnectionsAll ModelsAll FSS Series circulators have a bulkhead plate with the f
FSS Series Fountain Solution Systems Page 23IAE-600
Page 24 FSS Series Fountain Solution SystemsIAE-600
FSS Series Fountain Solution Systems Page 25IAE-600
Page 26 FSS Series Fountain Solution SystemsIAE-600Figure 5FSS Series Return Pump Curve3/8”1/2”
FSS Series Fountain Solution Systems Page 27IAE-600Figure 6FSS Series Return Pump Curve• 3/4”1”
Page 28 FSS Series Fountain Solution SystemsIAE-6003-3 Water Treatment ConsiderationsWater treatment is an integral part of the system. In somelocatio
Please note that our address and phone information has changed. Please reference this page for updated contact information. These manuals are obsolet
FSS Series Fountain Solution Systems Page 29IAE-600It is connected to the return of a central chill water system orto
Page 30 FSS Series Fountain Solution SystemsIAE-6003-7 FSS-R Series with Remote CondenserFSS-R Series circulators are shipped with a nitrogen holdingc
FSS Series Fountain Solution Systems Page 31IAE-600System ConfigurationThe system can be configured in any of the arra
Page 32 FSS Series Fountain Solution SystemsIAE-600Figure 8Figure 9(Figures 8 & 9 – Remote Condenser Piping Trap Locations)Sizing Refrigerant Line
FSS Series Fountain Solution Systems Page 33IAE-600Liquid Line SizingThe liquid line should be sized as small as possi
Page 34 FSS Series Fountain Solution SystemsIAE-600Figure 12Discharge Line Sizing30 – 65°F Leaving Water TemperatureDischarge Line Size (O.D.”)Eqiv. F
FSS Series Fountain Solution Systems Page 35IAE-600Calculate the amount of additional oil required by using thefollowi
Page 36 FSS Series Fountain Solution SystemsIAE-600The following table lists available glycol products available fromAEC, Inc.Part no. Description Par
FSS Series Fountain Solution Systems Page 37IAE-6004 Sequence of Operation4-1 Solution CircuitCooling water To Process
Page 38 FSS Series Fountain Solution SystemsIAE-600The refrigerant is compressed in the compressor and flows throughthe discharge line as a gas to the
FSS Series Fountain Solution Systems Page 3IAE-600Safety ConsiderationsAEC/FSS Solution Systems are designed to provid
FSS Series Fountain Solution Systems Page 39IAE-6004-4 Crankcase HeaterFSS-R Series models with remote condensers have
Page 40 FSS Series Fountain Solution SystemsIAE-6004-7 Fan Cycling SwitchFSS Series Air-Cooled Models OnlyFSS-A-5 and FSS-A-7.5 ModelsThese models hav
FSS Series Fountain Solution Systems Page 41IAE-600- Notes -
Page 42 FSS Series Fountain Solution SystemsIAE-6005 Setup Procedures5-1 Conductivity MeterGLI PRO-SERIES1) Press the menu key.2) Scroll down to con
FSS Series Fountain Solution Systems Page 43IAE-60025) The display will read “Zero In Dry Air?”, press enter.(screen
Page 44 FSS Series Fountain Solution SystemsIAE-60050) Scroll down to exit then press enter to go back to mainoperator screen.5-2 pH TRANSMITTERGLI
FSS Series Fountain Solution Systems Page 45IAE-60025) Scroll down to exit and press enter to return to sensor.26) Scr
Page 46 FSS Series Fountain Solution SystemsIAE-60039) Put the sensor in a cup of pH 7.00 (Make sure the threads onthe sensor are fully submerged)40)
FSS Series Fountain Solution Systems Page 47IAE-6006 Startup Checklists6-1 IntroductionFollow the check lists below fo
Page 48 FSS Series Fountain Solution SystemsIAE-600Scroll compressors are directionally dependent, i.e., they willonly compress in one rotational dire
Page 4 FSS Series Fountain Solution SystemsIAE-600Table of Contents1 General Information ... 71-1 Introd
FSS Series Fountain Solution Systems Page 49IAE-6007 Operation7-1 IntroductionStandard FSS Series circulators use a mi
Page 50 FSS Series Fountain Solution SystemsIAE-600Important!Do not change any of the control settings without consultingthe AEC Service Department. T
FSS Series Fountain Solution Systems Page 51IAE-600Detail “A”When programming the (H) high alarm and the (L) low alarm
Page 52 FSS Series Fountain Solution SystemsIAE-6007-4-2 7-second settings1.) In the operational mode, press the SEL key for 7 seconds untilthe displ
FSS Series Fountain Solution Systems Page 53IAE-6007-4-3 9-second settings1.) In the operational mode, press the SEL
Page 54 FSS Series Fountain Solution SystemsIAE-6007-5 Graphic Panel Indicators and SwitchesCompressor On Light (1.5 Ton Unit Only)The Compressor On l
FSS Series Fountain Solution Systems Page 55IAE-600Control Power Lighted SwitchThe green, lighted sustained-on Control
Page 56 FSS Series Fountain Solution SystemsIAE-6008 Optional CommunicationsStandard ProtocolThe communications function allows you to monitor and set
FSS Series Fountain Solution Systems Page 57IAE-600Stage 1: Freeze ProtectionStep Two (2) Press the SET Set key agai
Page 58 FSS Series Fountain Solution SystemsIAE-600Then: Press the Up Arrow key or the Down Arrow keyto toggle between C1 or H1 designations.T
FSS Series Fountain Solution Systems Page 5IAE-600Table of Contents5 Setup Procedures ...
FSS Series Fountain Solution Systems Page 59IAE-6009 Routine Maintenance9-1 LubricationQuarterlyGrease all blower bear
Page 60 FSS Series Fountain Solution SystemsIAE-600! CAUTIONDo not use compressed air to blow off a dirty filter.Using air will not clean very well, a
FSS Series Fountain Solution Systems Page 61IAE-6009-4 Maintaining the EvaporatorDirty heat exchange surfaces on the e
Page 62 FSS Series Fountain Solution SystemsIAE-6009-6 Preventive Maintenance ServiceFollow a systematic preventive maintenance program to help avoidc
FSS Series Fountain Solution Systems Page 63IAE-60010 Troubleshooting10-1 Cooling System (Chiller)Problem Possible cau
Page 64 FSS Series Fountain Solution SystemsIAE-600Problem Possible cause SolutionCompressor contactorholding coil open.Repair or replace.Defective pu
FSS Series Fountain Solution Systems Page 65IAE-60010-2 Cooling System (Heat Exchanger)Problem Possible cause Solution
Page 66 FSS Series Fountain Solution SystemsIAE-600
FSS Series Fountain Solution Systems Page 67IAE-600
Page 68 FSS Series Fountain Solution SystemsIAE-600
Page 6 FSS Series Fountain Solution SystemsIAE-600Charts and Figures1FSS Series 1.5 Hp Circulator 132FSS Series 3.5 Hp Circulator 143FSS Series 5 Hp C
FSS Series Fountain Solution Systems Page 69IAE-600
Page 70 FSS Series Fountain Solution SystemsIAE-60010-4 Circulating SystemProblem Possible cause SolutionCheck main breaker.Check fuse.Unit does not r
FSS Series Fountain Solution Systems Page 71IAE-60010-5 Return Pump TroubleshootingProblem Possible cause SolutionThe
Page 72 FSS Series Fountain Solution SystemsIAE-600Problem Possible cause SolutionChattering ocurs.Adjust the supply air pressureand discharge pressur
FSS Series Fountain Solution Systems Page 73IAE-600 Service Notes
Page 74 FSS Series Fountain Solution SystemsIAE-600Service Notes
FSS Series Fountain Solution Systems Page 75IAE-600Service Notes
Page 76 FSS Series Fountain Solution SystemsIAE-600Service Notes
FSS Series Fountain Solution Systems Page 77IAE-600I IndexPiping schematic, no tankmodels, 38Piping schematic, one-pum
Page 78 FSS Series Fountain Solution SystemsIAE-600Parts DepartmentCall toll-free 7am–6pm CST [800] 423-3183 or call [847] 273-7700The Parts Departmen
FSS Series Fountain Solution Systems Page 7IAE-6001 General Information1-1 IntroductionAEC, Inc. Fountain Solution Sys
WarrantyAEC, Inc. warrants all equipment manufactured by it to be free from defects in workmanship andmaterial when used under recommended conditions.
801 AEC Drive • Wood Dale, IL 60191-1198 USA(630) 595-1060 • Fax (630) 595-6641http://www.aecinternet.com
Page 8 FSS Series Fountain Solution SystemsIAE-6001-3 Models CoveredThis manual provides operation, installation, and maintenanceinstructions for AEC,